FPI 018/FPO 018 | up to 536m³/h (223x223mm)

网站首页 > FPI 018/FPO 018 | up to 536m³/h (223x223mm)
  • New air-flap outlet technology for high airflow
  • Easy mounting
  • Protection type test/Environmental rating by independent testing institutes (VDE & UL)
  • Two systems for optimal airflow (FPI/FPO)
  • Standard enclosure cut-out sizes (5 sizes)
  • One filter mat

Filter fans are used to provide an optimum climate in enclosures and cabinets with electrical/electronic components. The interior temperature of an enclosure can be reduced by channelling cooler filtered outside air into the enclosure thus expelling heated internal air. The resulting airflow prevents formation of localised hot pockets in installations and protects electronic components from overheating.

The Filter Fan Plus series uses a new airflap-outlet technology for the air outlet and thus reaches a high degree of airflow. A ratchet mechanism is used for mounting and provides high stability and tightness. Depending on the application there are two systems that are available - the FPI or FPO system. The FPI system is a standard installation with a filter fan in the lower part of the enclosure which ensures that fresh air is fed into the enclosure (airflow direction "In"). This system consists of a filter fan and exit filter. Whereas in the FPO system, the filter fan is located in the upper area of the enclosure to avoid heat buildups (airflow direction "Out"). The FPO system is composed of an intake filter and exit filter fan. The Filter Fan Plus series has been designed for indoor use.

TECHNICAL DATA

DOWNLOAD PDF

Axial fan, ball bearing

service life L10 at +40 °C (+104 °F): min. 56,000 h
rotor metal

Connection 3-pole clamp for 2.5 mm², clamping torque 0.8 Nm max.
Casing, hood, flaps plastic according to UL94 V-0, light grey;
UV light resistant according to UL746C (f1)
Enclosure cut-out 223 x 223+1mm
Mounting frame 4 built-in ratchet braces for mounting
(6 notches for wall thickness 1-4 mm).
Additional use of screws possible if needed1.
Filter mat G3 acc. to DIN EN 779, average arrestance Aa84 %
Filter material synthetic fibre with progressive construction,
temperature resistant to +100°C, self-extinguishing class F1,
moisture resistant to 100% RH, reusable
Operating temperature -25 to +65 °C (-13 to +149 °F)
Storage temperature -40 to +70 °C (-40 to +158 °F)
Operating/Storage humidity max. 75 % RH (non-condensing)
Protection type/Protection class IP54 / I (earthed)
Environmental rating UL/NEMA UL TYPE 12 / NEMA 12
Approvals VDE, UL File No. E234324, EAC
Note other voltages on request

1Drilling marks for screw mounting are indicated on mounting frame.

AIRFLOW DIRECTION "IN": FILTER FAN FPI 018

Art. No. Operating voltage Air volume,
free flow
Air volume
with exit filter
Current
consumption
(50/60 Hz)
Power
consumption
Average noise level
(DIN EN ISO 4871)
Depth in
enclosure
Weight
(approx.)
Filter mat
01873.0-30 AC 230 V, 50/60 Hz 305 m³/h 271 m³/h 300/340 mA 64 W 64 dB (A) 147 mm 2.4 kg G3
01873.9-30 AC 115 V, 50/60 Hz 332 m³/h 293 m³/h 600/700 mA 81 W 67 dB (A) 147 mm 2.4 kg G3

AIRFLOW DIRECTION "IN": EXIT FILTER FPI 118

Art. No. Depth in enclosure Weight (approx.) Air outlet
11873.0-00 46 mm

0.6 kg

air-flap outlet technology

AIRFLOW DIRECTION "OUT": FILTER FAN FPO 018

Art. No. Operating
voltage
Air volume,
free flow
Air volume
with intake filter
Current
consumption
(50/60 Hz)
Power
consumption
Average noise level
(DIN EN ISO 4871)
Depth in
enclosure
Weight
(approx.)
Air outlet
01883.0-00 AC 230 V, 50/60 Hz 536 m³/h 281 m³/h 300/340 mA 64 W 65 dB (A) 147 mm 2.4 kg air-flaps
01883.9-00 AC 115 V, 50/60 Hz 581 m³/h 310m³/h 600/700 mA 81 W 68 dB (A) 147 mm 2.4 kg air-flaps

AIRFLOW DIRECTION "OUT": INTAKE FILTER FPO 118

Art. No. Depth in enclosure Weight (approx.) Filter mat
11883.0-30 25 mm 0.5 kg G3 acc. to DIN EN 779, average arrestance Aa84 %

FILTER MAT FM 086

Filter class 215 x 215 mm Average arrestance Aa 1 packaging unit
G3 acc. to DIN EN 779 Art. No. 08636.0-00 84 % 5 pieces

TECHNICAL DRAWINGS


FPI 018/FPI 118

FPO 018/FPO 118